Description
Beckhoff EL3443 EtherCAT 3-Phase Power Measurement Terminal
The Beckhoff EL3443 integrates three-phase electrical measurements into an EtherCAT control system. It provides measured values for energy monitoring and auxiliary electrical systems in appropriately engineered wind energy installations.
Technical specifications
| Manufacturer | Beckhoff |
|---|---|
| Model | EL3443 |
| Inputs | Three voltage inputs and three current inputs |
| Measuring voltage | Maximum 480 V AC three-phase; UL terminal-to-neutral limit 277 V AC / 240 V DC |
| Current input | Maximum 1 A AC/DC; select compatible measuring transformers or transducers |
| Values | RMS voltage and current, active/reactive/apparent power and energy, frequency and power factor |
| Harmonic analysis | THD and harmonics up to the 40th order |
| Update interval | One mains period; 20 ms at 50 Hz |
| Typical E-bus current | 120 mA |
| Dimensions | 12 × 100 × 68 mm (W × H × D) |
| Operating temperature | −25 to +60 °C |
Application and selection
Requires a compatible EtherCAT controller/coupler and a correctly designed measurement circuit. The EL3443 is the 1 A input version. Higher-voltage turbine circuits require an appropriate voltage measurement interface within the terminal ratings. Specify other input variants separately.
Information for your quotation
Provide the controller/coupler, system voltage, CT ratio and secondary rating, required measured values, quantity and delivery postcode. Confirm wiring accessories, software configuration and commissioning scope.
Manufacturer image shows the EL3443 terminal and its connection diagram. Controllers, couplers and current transformers are separate unless included in the quotation.
Supply availability, included items, price, freight, lead time and warranty terms are confirmed in the written project quotation.