Description
LEM HAT 1000-S 1000 A AC/DC Current Transducer
The LEM HAT 1000-S is an open-loop Hall-effect current transducer for DC, AC and pulsed-current measurement. It provides an isolated measurement signal for suitably designed power converters, drives and renewable energy equipment.
Technical specifications
| Manufacturer | LEM |
|---|---|
| Model | HAT 1000-S |
| Nominal primary current | 1000 A RMS |
| Primary measuring range | ±2500 A at the specified supply conditions |
| Supply | Bipolar ±15 V DC, ±5% |
| Analogue output | ±4 V at ±1000 A, 25 °C and the specified load |
| Load resistance | Greater than 10 kΩ |
| Accuracy | ≤ ±1% of nominal current at 25 °C, excluding offset |
| Bandwidth | DC to 25 kHz (−3 dB); high-frequency thermal derating applies |
| Operating temperature | −40 to +105 °C; approval limits may be narrower |
| Mounting / mass | Baseplate or busbar mounting; 300 g |
Application and selection
For incorporation into engineered equipment with suitable signal conditioning, enclosure and insulation coordination. Select for both normal and peak current. The ±2500 A measuring range is distinct from the 1000 A nominal rating. Check frequency-related heating, conductor geometry and the secondary interface against the datasheet.
Information for your quotation
Provide nominal/peak current, waveform and frequency, conductor dimensions, operating temperature, power supply and receiving analogue-input requirements. Include quantity, connector needs and delivery postcode.
Manufacturer image shows the HAT 1000-S. Busbars, cables, connectors and measurement electronics are separate unless listed in the quotation.
Supply availability, included items, price, freight, lead time and warranty terms are confirmed in the written project quotation.